Skip to Content

What size breaker is needed for 240V?

When installing or upgrading electrical circuits that operate at 240 volts, it is crucial to use the properly rated circuit breaker to safely deliver power and protect the wiring from overload. Selecting the right size breaker for 240V circuits requires understanding some key factors like the circuit load, wire size, and maximum current draw according to electrical codes.

How to Calculate Circuit Load

The first step in choosing the right breaker size is calculating the total load on the circuit. This involves adding up the nameplate wattage or amp rating of all devices that will be powered by the circuit. For 240V circuits, the most common loads are:

  • Large appliances like ovens, ranges, cooktops, dryers
  • HVAC equipment like air conditioners and electric heaters
  • Water heaters
  • Baseboard and wall heaters

For example, if a 240V circuit will supply power to an electric oven rated at 8,000 watts, an electric water heater pulling 4,500 watts, and a pair of wall heaters at 1,000 watts each, the total load would be:

Oven: 8,000 watts
Water heater: 4,500 watts

Wall heater 1: 1,000 watts
Wall heater 2: 1,000 watts

Total circuit load: 14,500 watts

Converting Watts to Amps

Once the total wattage is known, it must be converted to amps to properly size the circuit breaker. This conversion is done using the following formula:

Amps = Watts / Volts

For our sample 240V circuit:

Total watts: 14,500
Volts: 240
Amps = 14,500 / 240 = 60.4 amps

Therefore, the load calculation tells us that a breaker rated for at least 60 amps is needed for this 240V circuit.

breaker-size-table.html

Wire Size Maximum Breaker Size
12 AWG 30 amps
10 AWG 40 amps
8 AWG 55 amps
6 AWG 75 amps
4 AWG 95 amps
3 AWG 115 amps
2 AWG 150 amps
1 AWG 180 amps

Considering Wire Size

In addition to the circuit load, the size of the wiring supplying the circuit also determines the maximum breaker size. Per electrical code, cables and wires must be protected from overload by a circuit breaker appropriately sized to the ampacity of the conductors.

The table above shows the maximum breaker sizes allowed for common 240V wire sizes per NEC guidelines. For example, a circuit wired using 10 AWG cable should not have a breaker larger than 40 amps.

In our sample circuit, if the wiring was 10 AWG, the next size up 60 amp breaker exceeded the limit for that wire. So the breaker would need to be downsized to the maximum of 40 amps allowed for 10 AWG.

Breaker Sizing Based on Load

Breakers for 240V circuits are commonly available in sizes from 20 amps up to 60 amps. In some cases, the minimum circuit breaker size required by the load calculation may not correspond to a standard breaker rating.

When this occurs, the next higher standard breaker size should be used. For example, if the load works out to 32 amps, choose a 40 amp breaker rather than a 30 amp unit.

It is permitted to round up to the next standard breaker size, but never round down. An undersized breaker will not properly protect the circuit.

Maximum Current per Code

The National Electrical Code (NEC) and local building codes also stipulate the maximum ampacity allowed on branch circuits and feeders. This limit takes precedence over both the load calculation and conductor ampacity.

For 240V residential circuits, some common maximum currents are:

  • 50 amps for kitchen small appliance circuits
  • 40 amps for individual appliance circuits
  • 100 amps for subpanels and service entrances

So even if the load calculation and wire size allowed a 70 amp breaker, the NEC maximum would take precedence, requiring a 50 or 60 amp breaker instead.

Conclusion

Choosing the proper circuit breaker size for 240V circuits involves:

  1. Calculating the total amps needed for the circuit load
  2. Selecting a standard breaker sized equal or above the load
  3. Ensuring the breaker rating does not exceed the ampacity for the wire size used
  4. Abiding by NEC maximums for branch circuits and feeders

Always consult the nameplates and installation manuals for equipment on the circuit to determine the correct voltage and wattage or amperage ratings. Performing careful load calculations and following code limitations will ensure the breaker used can deliver safe, reliable power to 240V electrical systems.